| UL Detail | Trade Detail | Description | F-Rating | T-Rating | L-Rating | W-Rating |
| F-C-0002 | F-C-0002 |
Max. 2" dia blank opening ()
| 1 or 2-hr | | | |
| F-C-1009 | F-C-1009 |
Max. 4" steel, cast iron, copper, conduit or EMT pipe (AS=0" to 1")
| 1 or 2-hr | | | |
| F-C-1059 | F-C-1059 |
Max. 6" steel, cast iron, conduit, max. 4" EMT, or max. 2" flexible steel conduit ()
| 1 or 2-hr | | | |
| F-C-1097 | F-C-1097 |
Max. 4" steel, copper, steel conduit or EMT pipe (AS=0" to 7/8") ()
| 1-hour | | | |
| F-C-1106 | F-C-1106 |
Max. 4" steel, cast iron, copper, conduit, or EMT ()
| 1-hour | | | |
| F-C-1134 | F-C-1134 |
Max. 4" cast iron closet flange with cast iron fittings ()
| 1-hour | | | |
| F-C-1135 | F-C-1135 |
Max. 1-1/2" cast iron P-trap with PVC, ABS, or brass bathtub waste/overflow fittings ()
| 1-hour | | | |
| F-C-1142 | F-C-1142 |
Max. 1" copper, steel, cast iron, steel conduit, or EMT ()
| 1-hour | | | |
| F-C-1147 | F-C-1147 |
Max. 1" flexible steel conduit or gas piping (max qty = 3) (AS=0" to 1-1/4") ()
| 1-hour | | | |
| F-C-2005 (cUL) | F-C-2005 (cUL) |
Max. 1” PEX or Aquarise CPVC Plastic Pipe (System tested to 50Pa Pressure Differential) ()
| 1 Hour | | | |
| F-C-2006 (cUL) | F-C-2006 (cUL) |
Max. 2” PVC, CPVC, ABS, or Aquarise CPVC Plastic Pipe (System tested to 50Pa Pressure Differential) ()
| 1 Hour | | | |
| F-C-2007 (cUL) | F-C-2007 (cUL) |
Max. 4” PVC, CPVC, or Aquarise CPVC Plastic Pipe (System tested to 50Pa Pressure Differential) ()
| 1 Hour | | | |
| F-C-2009 (cUL) | F-C-2009 (cUL) |
Max. 1-1/2” PVC or ABS bathtub fittings (System tested to 50Pa Pressure Differential) ()
| 1 Hour | | | |
| F-C-2010 (cUL) | F-C-2010 (cUL) |
Max. 4” PVC or ABS closet flange ()
| 1 Hour | | | |
| F-C-2011 (cUL) | F-C-2011 (cUL) |
Max. 4” PVC, ABS, CPVC, or 3” Aquarise CPVC Plastic Pipe (System tested to 50Pa Pressure Differential) ()
| 1 Hour | | | |
| F-C-2029 | F-C-2029 |
Max. 4" PVC or CPVC (closed or open) ()
| 2-hour | | | |
| F-C-2030 | F-C-2030 |
Max. 3" PVC, CPVC, ABS or FRPP (c,v) (AS=0" to 1/2") ()
| 1-hour | | | |
| F-C-2035 (cUL) | F-C-2035 (cUL) |
Max. 2" Fusiotherm or Climatherm PP (closed) ()
| 1-hour | 1-hour | | |
| F-C-2035 (cUL) | F-C-2035 (cUL) |
Max. 2" Fusiotherm or Climatherm PP (closed) ()
| 1-hour | | | |
| F-C-2071 | F-C-2071 |
Max. 2" PVC or CPVC (c,v) (AS=1/4" to 3/8") ()
| 1 or 2-hr | | | |
| F-C-2081 | F-C-2081 |
Max. 1" Polyethylene (PEX) SDR 9 Tubing (c,v) (AS=0" to 1/2") ()
| 1 or 2-hr | | | |
| F-C-2128 | F-C-2128 |
Max. 2" ABS, PVC or CPVC (c,v) (AS=0" to 5/8")
| 1 or 2-hr | | | |
| F-C-2142 | F-C-2142 |
Max. 2" ABS, PVC or CPVC (c,v) (AS=0" to 5/8") ()
| 1-hour | | | |
| F-C-2160 | F-C-2160 |
Max. 2" PVC or CPVC ()
| 1 or 2-hr | | | |
| F-C-2189 | F-C-2189 |
Max. 2" ABS or PVC tub drain (closed or open) ()
| 1-hour | | | |
| F-C-2203 | F-C-2203 |
Max. 4" ABS or PVC toilet flange (AS=0" to 1")
| 1-hour | | | |
| F-C-2204 | F-C-2204 |
Max. 1-1/2" PVC or ABS plastic pipe and Tub Drain Fittings ()
| 1-hour | | | |
| F-C-2205 | F-C-2205 |
Max. 1-1/2" PVC or ABS plastic pipe and Tub Drain Fittings ()
| 1-hour | | | |
| F-C-2230 | F-C-2230 |
Max. 1" PEX (closed or open) ()
| 1-hour | | | |
| F-C-2231 | F-C-2231 |
Max. 2" PVC, CPVC or ABS (closed or open) ()
| 1-hour | | | |
| F-C-2232 | F-C-2232 |
Max. 4" PVC or CPVC (c,v) with optional pipe coupling (AS=0" to 1/2")
| 1-hour | | | |
| F-C-2262 | F-C-2262 |
Max. 1-1/2" PVC or ABS plastic pipe and Tub Drain Fittings ()
| 1-hour | | | |
| F-C-2263 | F-C-2263 |
Max. 4" ABS or PVC toilet flange ()
| 1-hour | | | |
| F-C-2270 | F-C-2270 |
Max. 2" FlowGuard Gold or Blazemaster CPVC (c) (AS=0" to 5/8") ()
| 1-hour | | | |
| F-C-2310 | F-C-2310 |
Multiple 1" PEX (max qty = 3) ()
| 1 or 2-hr | | | |
| F-C-2334 | F-C-2334 |
Maximum 1" Polyethylene (PEX) SDR 9 Tubing (closed or open) ()
| 1-hour | | | |
| F-C-2335 | F-C-2335 |
Maximum 3" PVC, ABS, CPVC, or RNC (c,v) (AS=3/16" to 5/16")
| 1-hour | | | |
| F-C-2378 (cUL) | F-C-2378 (cUL) |
Max. 2” PVC, ABS, CPVC, Aquarise CPVC, or 1” PEX ()
| 1 Hour | | | |
| F-C-2382 | F-C-2382 |
Max. 4" PVC or ABS with branch line (c,v) (AS=0" to 1/2")
| 1-hour | | | |
| F-C-2389 | F-C-2389 |
Max. 3" PVC or CPVC (c,v) (AS=0" to 5/8")
| 1-hour | | | |
| F-C-3012 | F-C-3012 |
Cable bundle (various cables) ()
| 1 or 2-hr | | | |
| F-C-3044 | F-C-3044 |
Cable bundle (various cables) (AS=3/4") ()
| 1-hour | | | |
| F-C-3071 | F-C-3071 |
Cable bundle (various cables) (AS=0" to 1") ()
| 1-hour | | | |
| F-C-3074 | F-C-3074 |
Cable bundle (various cables) (AS=0" to 1")
| 1-hour | | | |
| F-C-3094 | F-C-3094 |
Multiple SER cables in slotted opening ()
| 1-hour | | | |
| F-C-5004 | F-C-5004 |
Max. 2" steel, copper, conduit or EMT pipes with max. 1/2" glass fiber or max. 3/4" AB/PVC insulation (AS varies) ()
| 1 or 2-hr | | | |
| F-C-5036 | F-C-5036 |
Max. 2" copper, or steel pipe with max. 1-1/2" glass fiber ()
| 1-hour | | | |
| F-C-5037 | F-C-5037 |
Max. 2" copper, or steel pipe with max. ¾" AB/PVC insulation ()
| 1-hour | | | |
| F-C-5065 | F-C-5065 |
Max. 4" copper, cast iron or steel pipe with ¾" AB/PVC insulation ()
| 1-hour | | | |
| F-C-5066 | F-C-5066 |
Max. 4" copper, cast iron or steel pipe with 1-1/2" glass fiber ()
| 1-hour | | | |
| F-C-7013 | F-C-7013 |
Max. 4" diameter sheet metal duct w/o damper (min 28Ga) ()
| 1-hour | | | |
| F-C-7025 | F-C-7025 |
Max. 10" diameter (min. 28 Ga) or 4" diameter (min. 30 Ga) sheet metal duct w/o damper ()
| 1-hour | | | |
| F-C-7036 | F-C-7036 |
Steel Grease or Air Duct with Firemaster DuctWrap by Thermal Ceramics ()
| 1 or 2-hr | | | |
| F-C-7042 | F-C-7042 |
Mechanical support mechanisms (strut, steel cable, steel rod, steel angle) ()
| 1-hour | | | |
| F-C-7043 | F-C-7043 |
Max. 12" x 10" sheet metal duct (AS=0" to 1") ()
| 1-hour | | | |
| F-C-8003 (cUL) | F-C-8003 (cUL) |
Insulated and non-insulated metallic, PEX lines, and cables ()
| 1 Hour | | | |
| F-C-8009 | F-C-8009 |
Single HVAC Line Set ()
| 1-hour | | | |
| F-C-8014 | F-C-8014 |
Single HVAC Line Set (AS=1/4" to 3/4") ()
| 1-hour | | | |
| F-C-8026 | F-C-8026 |
Double HVAC Line Set (pvc drain) ()
| 1-hour | | | |
| F-C-8032 | F-C-8032 |
Double HVAC Line Set (no pvc drain) ()
| 1-hour | | | |
| F-C-8044 | F-C-8044 |
Multiple penetrating items (metal, insulated, PEX, cables) through 14" x 5-1/2" block out (AS=0" to 1-1/2")
| 1-hour | X | | |